《9档变压器试验记录.docx》由会员分享,可在线阅读,更多相关《9档变压器试验记录.docx(4页珍藏版)》请在优知文库上搜索。
1、变压器试验报告安装位置1#站变试验性质交接型号Sl1-2000/10试验日期2016.05.29额定电压(KV)高压I(XXX)额定电流(A)高压115.5低压400低压2886.8额定容量(KVA)2000短路阻抗(%)5.81联接组别Dynll空载损耗(KW)/负载损耗(KW)/空载电流(%)/冷却方式ONAN出厂日期2014.09出厂编号02962制造厂家丹东欣泰变压比试验分接开关位置高压侧/低压侧实测变压比变压比误差()ABZabBC/bcCA/caAB/abBC/bcCA/ca127.47127.46127.471-0.11-0.14-0.10226.83626.83226.833-
2、0.15-0.16-0.16326.26226.25426.260+0.05+0.02+0.04425.62525.62325.617-0.00-0.01-0.03524.99524.98624.986-0.02-0.06-0.06624.35824.35424.350-0.07-0.09-0.10723.72323.71923.714-0.11-0.13-0.15823.14623.14023.140+0.09+0.07+0.07922.51122.50922.208+0.05+0.04+0.04高压绕组直流电阻(mA)别分接宜ABBCCA三相直流电阻不平衡率()1433.0433.9431
3、.90.462422.2423.0421.20.433412.3413.2411.30.464401.3401.2400.50.205390.4391.3389.80.386379.6380.5379.00.407368.7369.7368.20.418358.9359.9358.50.399348.2349.2347.90.37低压绕组直流电阻(mA)aoboCO三相直流电阻不平衡率()0.32180.32390.32711.63绝缘电阻试验试部位项目高压对低压及地低压对高压及地高压对低压铁心对地测试时间60S/15S60S/15S60S/15S60S绝缘电阻(GQ)250001300020
4、000/吸收比(%)/介质损失角试验典试部位项目高压对低压及地低压对高压及地高压及低压对地Cx(pf)/tg(%)()oC/tg(%)(20)oC/耐压试验项目测试部彳交流耐压直流耐压电压(KV)频率(HZ)时间(min)电压(KV)时间(min)泄漏电流(A)高压对低压及地28501/低压对高压及地4501/备注变压器试验报告安装位置2#站变试验性质交接型号Sl1-2000/10试验日期2016.05.29额定电压(KV)高压I(XXX)额定电流(A)高压115.5低压400低压2886.8额定容量(KVA)2000短路阻抗(%)5.85联接组别Dynll空载损耗(KW)/负载损耗(KW)/
5、空载电流(%)/冷却方式ONAN出厂日期2014.09出厂编号02963制造厂家丹东欣泰变压比试验分接开关位置高压侧/低压侧实测变压比变压比误差()ABZabBC/bcCA/caAB/abBC/bcCA/ca127.47327.46427.460-OJO-0.13-0.14226.83726.83426.832-0.14-0.15-0.16326.26026.25626.252+0.04+0.02+0.01425.62825.62425.619+0.01-0.00-0.02524.99224.98524.982-0.03-0.06-0.07624.35724.35124.354-0.08-0.
6、10-0.09723.72023.72023.716-0.13-0.12-0.14823.14323.14423.145+0.08+0.08+0.09922.51222.50722.507+0.05+0.03+0.03高压绕组直流电阻(mA)别分接宜ABBCCA三相直流电阻不平衡率()1432.0430.6431.90.322421.3419.8421.00.363411.4409.9411.10.374400.5399.1400.40.355389.6388.3389.60.336378.9377.6378.90.347368.1366.9368.20.358358.4357.2358.60
7、.399347.7346.7348.00.37低压绕组直流电阻(mA)aoboCO三相直流电阻不平衡率()0.32030.32230.32551.61绝缘电阻试验试部位项目高压对低压及地低压对高压及地高压对低压铁心对地测试时间60S/15S60S/15S60S/15S60S绝缘电阻(GQ)300001000030000/吸收比(%)/介质损失角试验典试部位项目高压对低压及地低压对高压及地高压及低压对地Cx(pf)/tg(%)()oC/tg(%)(20)oC/耐压试验项目测试部彳交流耐压直流耐压电压(KV)频率(HZ)时间(min)电压(KV)时间(min)泄漏电流(A)高压对低压及地28501/低压对高压及地4501/备注